User settings

Setting the ventilation unit

Switch off the ventilation device

If you need to open the doors of the ventilation unit in connection with maintenance or changing filters, do not forget to switch off the ventilation unit. You do this under the menu item "Operation".

13

When the ventilation unit is switched off, this icon is displayed on the main control panel screen in the top right corner.

ATTENTION_YELLOW

Before touching electrical installations, make sure the power supply is switched off.

ATTENTION_YELLOW

It is important that the ventilation unit is not switched off for long periods, as this can cause problems with condensation in the duct system.

DEVICE ON/OFF
Device on/off Settings Off / On
Description The ventilation unit should be switched off before opening the doors during maintenance.

Operating function

You can set the unit to "Auto", "Heating" or "Cooling".

ATTENTION_YELLOW

The "Heating" and "Cooling" functions have priority over the weekly programme. If a weekly programme is activated, the mode automatically switches to "Auto" the next time the weekly programme changes.

Operating function
Operating function Settings Auto - Cooling - Heating
Standard Auto
Description Auto: The device operates according to the selected values.
Cooling: The device operates according to the selected values. However, cooling is possible in winter mode if the requirements for cooling are present.
Heating: The unit operates in accordance with the selected values, but the bypass valve cannot be opened and active cooling cannot be activated, even if the requirements for cooling are present.

Alarm

Warnings and alarms can be read under the "Alarm" menu item. This is also where you reset them once the problem is resolved.

ATTENTION_RED

If an alarm or alert is active, the alarm icon appears in the top-right corner of the control panel.

Alarm
Alarm number and name Description When you press the alarm, the following information appears:
- Alarm ID number
- Alarm type
- Critical alarm or warning (The alarm list informs you how to act).
ATTENTION_YELLOW

Until the problem is resolved, the alarm or alert remains active. When the problem is solved, you can reset the alarm or alert by pressing "Clear alarm".

Show data

You can read the current operating data of the ventilation unit. This allows you to check the proper operation of the unit and identify the cause of any alarms.

Show data
Operating state Description Indicates which operating mode the ventilation unit is in.
Bypass Description Indicates whether the bypass valve is open or closed.
Anode Description Indicates whether the anode is OK. If it is faulty, it must be replaced.
T1 Outside air Description Shows the outside temperature before pre-heating.
T2 Air supply Description Displays the supply air temperature if no post-heating element is installed.
T4 Blowout Description Shows the discharge temperature in the exchanger.
T5 Capacitor Description Displays the condenser temperature.
T6 Evaporator Description Displays evaporator/exhaust air temperature.
T7 Air supply Description Shows the temperature of the supply air if a post-heating element is installed.
T10 Return air space Description Displays the current room temperature measured in the return air.
T11 Top hot water Description Displays the current temperature at the top of the hot water tank. Controls additional electric heating.
T12 Soil hot water Description Displays the current temperature at the bottom of the hot water tank. Controls the heat pump.
Humidity Description Shows the current humidity level in the house.
CO2 level Description Shows the current CO2 level in the house (only if installed).
Supply fan Description Displays the current speed level of the supply air fan.
Extractor fan Description Displays the current extraction fan speed level.
Information about the unit Description Press for more information about the ventilation unit.
Unit type Description Shows which type of ventilation device it is.
Software version Description Displays the software version of the ventilation unit.
Panel software Description Displays the software version of the control panel.

Date / time

It is important to set date and time correctly. It makes it easier to detect possible failures when an error is reported. When logging data, it is important to be able to track history. You set the time in the settings menu.

Date/time
Year Description Press "Year" on the panel and select the current year.
Month Description Press "Month" on the panel and select the current month.
Bye Description Press "Day" on the panel and select the current day of the week.
Hour Description Press "Hour" on the panel and select the current hour of the day.
Minute Description Press "Minute" on the panel and select the current minute.

Weekly programmes

A weekly programme allows you to programme the ventilation unit to run at fixed times of the day and week according to certain settings.

15

On the main control panel screen, in the top right corner, the Week Programme icon appears when it is active.

Weekly programme
Select weekly programme Settings OUT - 1 - 2 - 3
Standard OUT
Description The controls allow you to set 3 programmes for different situations, e.g:
- Normal operation
- holiday operation
Edit programme Description The selected weekly programme is now active and can be edited.
Monday Settings Here, the weekday is selected.
Function 1 Settings Here you select the function you want to edit.
Start time Settings Hours and minutes
Standard 6:00
Description Set the time at which the programme starts. The programme runs with the set values until the next change in the Week programme.
Ventilation Settings Level 1 - Level 2 - Level 3 - Level 4 - OFF
Standard Level 3
Description Select the desired level of fan speed here.
Temperature Settings 5 to 40 °C
Standard 22 °C
Description Set the desired room temperature here.
Copy for the next day Description Once the values for the Monday programme are set, it is possible to copy them to the next day.
The same settings are made for all functions.
Reset programme settings You can reset the programme by selecting the "Approve" icon.

Domestic hot water

The settings for hot water production are set at the factory, but it may be necessary to adjust them according to the user's needs.

Domestic hot water
Additional electric heating hot water Settings OFF | 5 to 85 °C
Standard 30 °C
Description OFF: The supplementary electric heating is switched off by the user.
5 - 85 ºC: Indicates below which temperature (T11) the supplementary electric heater should help heat domestic hot water.
Hot water temperature Settings OFF - 5 to 60 °C
Standard 45 °C
Description Off: Hot water production is switched off by the user.
5 - 60 ºC: Indicates below which temperature (T12) the compressor should produce hot water.
Day for legionella treatment Settings NO - Mon - Thu - Wed - Fri - Sat - Sun
Standard NO
Description This specifies whether the unit should perform weekly legionella treatment.*
Legionella temperature Settings 50 to 70 °C
Standard 65 °C
Description Legionella treatment temperature

* If a weekday is selected, the legionella function will start at 1:00 at night and heat the domestic hot water to 65 °C. The function only works if the additional electric heating is activated.

Reheating element

This menu item is only available if an electric reheating element or a water reheating element is installed, and if it is activated in "Service settings".

ATTENTION_YELLOW

An after-heating element is not included as standard. However, you can order it as an extra and it can also be retrofitted.

If you want to be able to control the temperature of the supply air, you should install a post-heating element. This allows you to control the temperature of the supply air regardless of the outside temperature. The post-heating element can also contribute to heating the home.

Reheating element
Switch on / switch off Settings OFF - ON
Standard OUT
Description Here the user can switch on and off the reheating element.

Cooling

The unit can cool the house via bypass cooling and/or active cooling via the heat pump. To put the unit in cooling mode, it must operate in summer mode, or you must activate cooling in the "Operation mode".

Bypass cooling: If the room temperature, measured in the return air, is higher than the cooling set point -2 ºC and the outside temperature is lower than the room temperature, the bypass will open and start bypass cooling.

The bypass closes again as soon as the room temperature reaches the desired level +1 ºC.

If the outdoor temperature is higher than the room temperature and cooling becomes necessary, the bypass will not open. However, the unit will start the recovery of cooling through the heat exchanger where the outdoor air is cooled by the return air.

Active cooling: If the room temperature (measured in the return air) is higher than the target room temperature + the cooling setpoint, the compressor starts and the supply air starts actively cooling. The compressor stops when the room temperature falls below the cooling setpoint -1ºC.

Cooling
Cooling set point Settings OFF - +1 - +2- +3 - +4 - +5 - +7 - +10 ºC
Standard OUT
Description Off: Active cooling is disabled.
Set point + X ºC: Specifies when active cooling should start. The set point for the desired room temperature is selected on the front of the panel.
Ventilation in cooling mode Settings OUT - 2 - 3 - 4
Standard OUT
Description Off: The fan speed level does not change when the unit switches to cooling mode.
Level 2-4: Select the fan speed level you want the unit to switch to when in cooling mode. This already happens during bypass cooling.
Priority Settings Water - Air supply
Standard Water
Description This indicates whether the cooling function should have a higher priority than domestic hot water production. *

* When domestic hot water is needed, the heat pump gives priority to domestic hot water production and does not cool. However, it opens the bypass valve when cooling is required.

If cooling is given a higher priority than hot water, the unit will cool the supply air and store the heat in the hot water tank during that period. Domestic hot water will be heated, but not as quickly as usual for hot water production.

Humidity control

The main purpose of ventilation is to remove moisture from the house to avoid damaging the building, and to achieve a good indoor climate. During long periods with sub-zero temperatures, humidity in the house can drop to levels that are critical for the building and indoor climate. Wooden floors, furniture and walls can be damaged by very dry air, which also blows up dust, resulting in a poor indoor climate.

This is remedied by an integrated humidity control system that maintains good, relative humidity. When the average humidity in the house drops below a certain level (set at 30% by default), ventilation can be reduced. This will usually only be for a short period of time. This helps prevent the humidity in the house from falling further.

The humidity control also has a function that allows more ventilation should the humidity increase, for example when taking a bath. The risk of mould in the bathroom is reduced and the bathroom mirror will rarely steam up.

Humidity control tracks the average humidity level measured over the past 24 hours. Thus, the system automatically adjusts to summer and winter conditions.

Humidity control
Vent. low humidity Settings Level 1 - Level 2 - Level 3 - OFF
Standard Level 1
Description When the current humidity drops below the low humidity level, the ventilation unit switches to the set ventilation level.
OFF means venting at low humidity is disabled.
Low humidity Settings 15 to 45%
Standard 30%
Description When the current humidity falls below this value, the ventilation level set above is activated.
Vent. high humidity Settings Level 2 - Level 3 - Level 4 - OFF
Standard Level 3
Description In case of high humidity, e.g. when bathing, the unit switches to the set fan speed.
Off means that the High Humidity Ventilation function is disabled.
Max. time high humidity Settings 1 to 180 min. - OFF
Standard 60 min.
Description The "High Humidity" function stops when the actual humidity is less than 3% above the average humidity.

However, this time limit will stop operation if it fails within the set time.

Off means the Max time at high humidity function is not activated.

CO2 monitoring

This menu is only displayed if a CO2 sensor is installed and the function is selected under Service settings.

If the number of people using a building varies widely, controlling ventilation via the CO2 level in the exhaust air can be a good solution. This feature is often used in offices and schools where usage varies widely throughout the day and week.

ATTENTION_YELLOW

A CO2 sensor is not a standard part of all ventilation units, but can be purchased as an accessory.

CO2 monitoring
Vent. high CO2 Settings Level 2 - Level 3 - Level 4 - OFF
Standard Level 3
Description Here you set the fan speed at which the unit should operate at high CO2 levels.
OFF means this function is disabled.
High CO2 level Settings 650 to 2500 ppm
Standard 800 ppm
Description Here you set the CO2 level at which the unit should switch to a higher fan stage.
Normal CO2 level Settings 400 to 700 ppm
Standard 600 ppm
Description Here you set the CO2 level at which the unit should switch to normal fan speed level.

Air exchange

You can prevent low humidity in the home by reducing ventilation during low outdoor temperatures. This function is useful, for example, in countries with regular frosts or at high altitudes in the mountains where the outside air is very dry.

Air exchange
Ventilation type Settings Water - Comfort - Energy
Standard Comfort
Description Water: Here, the supply air fan stops working as long as sanitary water heating is required.
Energy: This is where operation is optimised.
Comfort: Here, air exchange is always balanced.
Comfort Description You have selected comfort where the fan speed for supply and return air is always the same.
Low temp. compr. start Settings 0 to -15 °C - OFF - 0 to 15 °C
Standard OUT
Description Here you specify whether the heat pump should start up at low outside temperatures, even if no heating is required.
OFF means the function is disabled.
Level winter low Settings Level 1 - Level 2 - Level 3 - OFF
Standard OUT
Description Here you specify the fan speed level at which you want the ventilation unit to operate at low outdoor temperatures.
OFF means the function is disabled.
Temperature winter low Settings -20 to 10 °C
Standard 0 °C
Description Here you specify the outside temperature at which you want the "Winter low" function to be activated.
Water Description You have selected Water, which means that the supply air fan stops as long as water is heated for domestic use. When the appliance is in cooling mode, the supply air does not stop.
Low temp. compr. start Settings 0 to - 15 °C - OFF - 0 to 15 °C
Standard OUT
Description Here you specify whether the heat pump should start up at low outside temperatures, even if no heating is required.
OFF means the function is disabled.
Level winter low Settings Level 1 - Level 2 - Level 3 - OFF
Standard OUT
Description Here you specify the fan speed level at which you want the ventilation unit to operate at low outdoor temperatures.
OFF means the function is disabled.
Temperature winter low Settings -20 °C to 10 °C
Standard 0 °C
Description Here you specify the outside temperature at which you want the "Winter low" function to be activated.
Energy Description You have chosen Energy, which ensures energy-optimised operation by controlling the supply air quantity against the set temperature curve.
Low temperature curve Settings 15 °C to 46 °C
Standard 38 °C
Description With "curve control", the supply air will always be constant as it is controlled with a fan speed up or down.
Min. curve is level 1.
High temperature curve Settings 39 °C to 60 °C
Standard 50 °C
Description With "curve control", the supply air will always be constant as it is controlled with a fan speed up or down.
Max curve is level 4.
Low temp. compr. start Settings 0 °C to -15 °C - OFF - 0 to 15 °C
Standard OUT
Description Here you specify whether the heat pump should start up at low outside temperatures, even if no heating is required.
OFF means the function is disabled.
Level winter low Settings Level 1 - Level 2 - Level 3 - OFF
Standard OUT
Description Here you specify the fan speed level at which you want the ventilation unit to operate at low outdoor temperatures.
OFF means the function is disabled.
Temperature winter low Settings -20 to 10 °C
Standard 0 °C
Description Here you specify the outside temperature at which you want the "Winter low" function to be activated.

Capacitor curve control

Filter alarm

ATTENTION_YELLOW

It is important to change the filters regularly and when necessary. Dirty filters reduce the efficiency of the ventilation unit and lead to a worse indoor climate and higher energy consumption.

From the factory, the filter alarm is set to indicate filter replacement every 90 days. You can adjust the timer according to the level of contamination in the area where the ventilation unit is installed.

If someone in the household has a pollen allergy, it is advisable to install a pollen filter in the outdoor air intake.

Filter alarm
Days to change Settings NONE - 30 - 60 - 90 - 180 - 360
Standard 90 days
Description The number of days between filter changes can be set as required.

Temperature control

If you have not installed an after-heating element, use the settings to control the bypass valve.

It is necessary to install an after heater if you want to control the temperature of the supply air and if you want it to contribute to heating the home. With an after heater, you can control the temperature of the supply air regardless of the outside temperature.

You can install an external electric or water post-heating element in the air supply duct.

ATTENTION_YELLOW

During periods when heating is not required in the home, the supply air temperature may drop below the minimum temperature.

Temperature control
Min. supply air summer Settings 5 to 16 °C
Standard 14 °C
Description Here you set the minimum supply air temperature the ventilation unit should be able to deliver during summer, when the unit is in heating mode.
Min. supply air winter Settings 14 to 22 °C
Standard 16 °C
Description Here you set the minimum supply air temperature that the ventilation unit should be able to deliver in winter when the unit is in heating mode.

NB: Only possible if a reheater is installed.
Max. supply air summer Settings 5 to 50 °C
Standard 35 °C
Description Here, you set the supply air temperature that the ventilation unit should be able to deliver maximum when heating is required.

Note: This option is displayed only if an after heater is installed and activated.
Max. supply air winter Settings 5 to 50 °C
Standard 35 °C
Description Here, you set the supply air temperature that the unit should be able to deliver maximum in winter.

Note: This option is displayed only if an after heater is installed and activated.
Summer/winter service Settings 5 to 30 °C
Standard 12 °C
Description Here you set the temperature for switching between summer and winter operation.

- If the outside temperature is higher, the unit operates in summer mode.
- When the outdoor temperature is lower, the unit operates in winter mode.

Language

The default language for the ventilation unit is Danish. You can change the texts to other languages in the settings menu.

Language
Dansk Description Select the desired language on the panel.